SECTION 07 46 23

WOOD SIDING

SPECIFIER NOTEThis guide specification is written in CSI SectionFormat and PageFormat for editing by the design professional. Specifier notes (shaded) and bracketed options [ ]✕ must be edited or deleted before issue. Highlighted items [...]✕ are manufacturer data to be confirmed by Nova USA Wood Products before this document is published.
SPECIFIER NOTEThis section is based on products of Nova USA Wood Products, 3821 24th Avenue, Forest Grove, OR 97116. Tel: (503) 419-6407. Email: sales@novausawood.com. Web: www.novausawood.com. BIM files for rainscreen, decking and clip profiles, profile drawings, installation guides and warranties are at www.novausawood.com/downloads. Technical support, samples and AIA continuing education presentations are available from the manufacturer.
SPECIFIER NOTEThis section covers two exterior wood siding systems. System A: rainscreen siding on Nova ExoClad QuickClip concealed clips over a ventilated cavity. System B: tongue-and-groove pattern siding face-nailed horizontally over wood structural panel sheathing; with Ambara, System B is the assembly listed by the California State Fire Marshal for Wildland-Urban Interface use. Retain one or both systems. For exterior trim, fascia and soffits, see Section 06 20 13. For interior paneling, see Section 06 42 00.

PART 1 - GENERAL

1.1SUMMARY
A.Section Includes:
1.[System A: Wood rainscreen siding, [horizontal] [vertical] [diagonal] application, with concealed clip attachment and 3/4-inch (19 mm) ventilated air space.]✕
2.[System B: Tongue-and-groove pattern siding, face-nailed horizontally over wood structural panel sheathing.]✕
3.Concealed siding clips, fasteners, vent strips, trim and accessories.
4.[Factory-applied] [Field-applied] penetrating oil finish.
B.Related Requirements:
1.Section 06 10 00 "Rough Carpentry" for framing and blocking.
2.Section 06 16 00 "Sheathing."
3.Section 06 20 13 "Exterior Finish Carpentry" for trim, fascia and soffits.
4.Section 07 25 00 "Weather Barriers."
5.Section 07 62 00 "Sheet Metal Flashing and Trim."
6.Section 09 93 00 "Staining and Transparent Finishing" for field-applied ExoShield finish.
1.2REFERENCES
A.ASTM D143 - Standard Test Methods for Small Clear Specimens of Timber.
B.ASTM D1037 - Standard Test Methods for Evaluating Properties of Wood-Base Fiber and Particle Panel Materials (water-soak swelling).
C.ASTM D1413 - Standard Test Method for Wood Preservatives by Laboratory Soil-Block Cultures; AWPA E10.
D.CEN/TS 15083-1 - Durability of Wood and Wood-Based Products: Determination of the Natural Durability of Solid Wood against Wood-Destroying Fungi.
E.EN 350 - Durability of Wood and Wood-Based Products: Testing and Classification.
F.ASTM E84 - Standard Test Method for Surface Burning Characteristics of Building Materials.
G.ASTM D2898 - Standard Practice for Accelerated Weathering of Fire-Retardant-Treated Wood for Fire Testing.
H.ASTM E2768 - Standard Test Method for Extended Duration Surface Burning Characteristics of Building Materials (30 min Tunnel Test).
J.California State Fire Marshal SFM Standard 12-7A-1 - Exterior Wall Siding and Sheathing.
K.WCLIB Standard No. 17 - Grading Rules for West Coast Lumber.
L.AWPA U1 - Use Category System: User Specification for Treated Wood.
M.AWPA T1 - Processing and Treatment Standard.
1.3PERFORMANCE REQUIREMENTS
A.Ventilated Cavity (System A): System shall maintain a continuous 3/4-inch (19 mm) air space behind siding, open at top and bottom, for drainage and drying.
B.Wind Load: Siding, clips and fasteners shall resist design wind pressures indicated on Drawings. Clips at every stud or blocking, not more than 16 inches (406 mm) o.c.
C.Fire-Test-Response Characteristics:
SPECIFIER NOTEExterior wall coverings of combustible material are limited by construction type, height and fire separation distance under IBC Chapter 14 and Chapter 7. Verify allowances with the authority having jurisdiction. WUI: Nova's CSFM BML Listing 8140-2377:0003 (SFM 12-7A-1, Western Fire Center report 25068r2) covers Ambara nominal 1x6 and wider T&G siding face-nailed horizontally over 7/16-inch OSB sheathing. It does not cover this clip-attached, open-cavity rainscreen assembly. The rainscreen assembly has not been tested to SFM 12-7A-1. In WUI areas, specify the listed T&G assembly or obtain approval from the authority having jurisdiction.
1.Surface-Burning Characteristics: Flame-spread index and smoke-developed index per ASTM E84 for each species as listed in Part 2 [Class A] [Class B] [Class C].
2.[Ignition-Resistant Treatment: Provide [Inari] [Ambara] factory pressure-treated with an exterior-type fire-retardant treatment complying with AWPA U1 Use Category UCFB (exterior, above ground) and treated in accordance with AWPA T1, kiln dried after treatment (KDAT) to 15 percent maximum moisture content, meeting: IBC Section 2303.2 fire-retardant-treated wood; ignition-resistant material per IWUIC Section 503.2 and CBC Chapter 7A; ASTM E84 / UL 723 flame-spread index 25 or less with the test extended to 30 minutes per ASTM E2768 and flame front not progressing more than 10.5 feet (3.2 m) beyond the burner centerline; no increase in classification after accelerated weathering per ASTM D2898. Evaluation: current ICC-ES or UL evaluation report and CSFM BML listing of the treater used [report and listing numbers by treater]✕. Each piece shall bear the mark of the independent inspection agency indicating the extended 30-minute ASTM E84 test. Supply a certificate of treatment with each shipment identifying the treater, evaluation report and listing.]✕
3.[Wildland-Urban Interface: Provide System B with Ambara, listed under CSFM BML Listing 8140-2377:0003 (SFM 12-7A-1), installed as listed.]✕
SPECIFIER NOTECSFM Building Materials Listings are renewed annually. Verify that the listing is current in the CSFM BML database at time of bid.
1.4ACTION SUBMITTALS
A.Product Data: For each product, include species, grade, profile, moisture content, physical and mechanical properties, and finish.
B.Shop Drawings: Show layout, profiles, attachment, clip and fastener spacing, joints, terminations, penetrations, and transitions to adjacent construction.
C.Samples for Initial Selection: Boards of each species, 5-1/2 inches (140 mm) wide, milled to clip profile, unfinished and with each ExoShield color selected.
D.Samples for Verification: Two boards of each species, profile and finish, not less than 12 inches (305 mm) long, plus one ExoClad QuickClip with fastener.
1.5INFORMATIONAL SUBMITTALS
A.Product Test Reports: From a qualified independent testing agency, indicating compliance with the performance requirements in Part 2, including fire-test-response characteristics.
B.Manufacturer's Installation Instructions: Current editions of the manufacturer's published installation guides referenced in Part 3.
C.Legality Documentation: Manufacturer's declaration that wood products are legally harvested and imported in compliance with the U.S. Lacey Act, maintained under the manufacturer's written Lacey Act Compliance Program (supplier due-diligence questionnaire covering species, country and region of harvest, harvest permits and CITES status; PPQ 505 import declarations; seven-year record retention). Documentation available on request.
D.Sustainability Documentation: Manufacturer's LEED v4/v4.1 alignment statement (www.novausawood.com/PDFs/Nova-LEEDS-Alignment.pdf).
SPECIFIER NOTENova's source mills hold FSC or PEFC certification, but Nova does not currently hold its own chain-of-custody certificate, so products are not sold with a certified claim and do not contribute to LEED MR sourcing credits as supplied. Where certified wood is required, contact Nova before bid to arrange certified supply.
E.Acclimation Record: Dated moisture-meter readings, with photographs, of boards selected at random throughout each delivery, and the site equilibrium moisture content, submitted before installation begins.
1.6CLOSEOUT SUBMITTALS
A.Maintenance Data: Manufacturer's published maintenance guide for each product and finish.
B.Warranty: Executed manufacturer's warranty as specified.
1.7QUALITY ASSURANCE
A.Manufacturer Qualifications: A firm with not less than 10 years of experience supplying products of the type specified.
B.Installer Qualifications: A firm with not less than one year of experience installing wood rainscreen siding in solid wood (not composite or PVC) of similar scope, familiar with the manufacturer's installation guides referenced in Part 3.
C.Mockups: Build mockup not less than 8 feet (2.4 m) wide by 8 feet (2.4 m) high, including an outside corner, a window opening, top and bottom vents, and selected finish to verify selections, workmanship, attachment and finish.
1.Approval of mockup does not constitute approval of deviations from the Contract Documents.
2.Approved mockup may become part of the completed Work if undisturbed at Substantial Completion.
D.Preinstallation Conference: Conduct at Project site with Installer and manufacturer's representative. Review storage, acclimation and the Acclimation Record.
1.8DELIVERY, STORAGE, AND HANDLING
A.Deliver materials with packing list identifying species, grade, profile, quantity and lengths, and accessories.
B.Store materials flat, off the ground on level supports not less than 4 inches (100 mm) above grade, under breathable cover that sheds water while allowing air circulation. Do not wrap tightly in polyethylene.
C.Acclimate materials at Project site in accordance with manufacturer's "Acclimating Siding and Decking" guide (https://www.novausawood.com/PDFs/acclimating-siding-decking.pdf) until average moisture content is within 2 percent of the site equilibrium moisture content (EMC). Do not base acclimation on time alone.
1.Restack with stickers not less than 3/4 inch (19 mm) thick spaced not more than 12 inches (305 mm) apart; keep stacks out of direct sun and water, with covers held off the stack.
2.Verify with a moisture meter on boards selected at random throughout the stack; record, date and photograph readings and submit to the Architect as the Acclimation Record before installation begins.
D.Keep siding dry prior to installation. Protect factory-finished material from abrasion and UV exposure until installed.
E.Tannin Bleed (Batu, Bangkirai, Torem, Ipe): These species contain water-soluble extractives (tannins) that bleed when wet and can stain concrete, masonry, stone and light-colored adjacent finishes. Store away from these surfaces with the ground beneath covered, protect adjacent surfaces from runoff during construction, and clean any staining in accordance with the manufacturer's maintenance guide. Bleeding diminishes after the first several rains.
SPECIFIER NOTEMelywood is modified to neutralize its tannins and does not bleed. Where staining of adjacent masonry or light-colored finishes is a concern, consider Melywood.
1.9FIELD CONDITIONS
A.Do not install siding until weather barrier, flashings and window and door installations are complete and approved.
1.10WARRANTY
SPECIFIER NOTEManufacturer's warranties apply to residential and commercial projects and cover material only; labor is excluded. Confirm terms against the current published warranty documents before issue.
A.Thermally Modified and Tannin-Free Siding (Ambara, Inari, Korina, Melywood): Manufacturer's limited warranty that the wood will not suffer structural damage from rot and decay for 25 years from date of purchase. Remedy at manufacturer's option: replacement boards, repair, or cash compensation prorated by years in service; labor excluded. Register within 90 days after installation per manufacturer's procedure (www.novausawood.com/warranty-registration), with dealer receipt and project photo; include the registration confirmation with closeout submittals. Reference: Nova Thermally Modified Wood Warranty (https://www.novausawood.com/PDFs/nova-thermal-modified-warranty-2026.pdf).
B.Tropical Hardwood Siding (Batu, Bangkirai, Torem, Ipe): Manufacturer's limited warranty that the wood will not suffer structural damage from rot, decay or termites for 25 years from date of purchase. Remedy at manufacturer's option: replacement boards, repair, or cash compensation prorated by years in service; labor excluded. Register within 90 days after installation per manufacturer's procedure (www.novausawood.com/warranty-registration), with dealer receipt and project photo; include the registration confirmation with closeout submittals. Reference: Nova Durable Tropical Hardwood Warranty (https://www.novausawood.com/PDFs/nova-durable-tropical-hardwood-warranty-2026.pdf).
SPECIFIER NOTEFijian Mahogany is not covered by a manufacturer's warranty.
C.Clips: Manufacturer's limited lifetime warranty for ExoClad QuickClip, as defined in the manufacturer's published warranty. Register the warranty in the Owner's name within 90 days of purchase at www.novausawood.com/warranty-registration and include the registration receipt with closeout submittals. Reference: ExoClad QuickClip Warranty (https://www.novausawood.com/PDFs/nova-siding-clips-warranty.pdf).

PART 2 - PRODUCTS

2.1MANUFACTURERS
SPECIFIER NOTEChoose ONE of the two options below. Option 1 (basis of design) is recommended for most public and private work: it names Nova while allowing the contractor to propose an equal under Division 01. Use Option 2 (proprietary) only where the Owner permits a sole-source specification.
A.Basis-of-Design Product: Subject to compliance with requirements, provide [Nova ExoClad QuickClip Rainscreen Siding System (System A)] [Nova T&G pattern siding (System B)] with [Ambara] [Inari] [Korina] [Melywood] [Batu] [Bangkirai] [Torem] [Ipe] [Fijian Mahogany] siding by Nova USA Wood Products, Forest Grove, Oregon; www.novausawood.com.
1.Comparable Products: Products of other manufacturers will be considered when they meet every performance requirement of this Section, documented by test reports from independent laboratories, and are approved by the Architect in accordance with Section 01 60 00 - Product Requirements.
2.Substitutions: Not permitted.
B.Source Limitations: Obtain each product type, including clips, fasteners, end sealer and factory finish, from a single source through one manufacturer.
2.2SIDING SPECIES
SPECIFIER NOTERetain one or more species. Species are listed with the physical properties that make them qualify; retain the values with the species selected so that comparable products must meet them.
A.Thermally Modified Ayous (Basis of Design: Nova Ambara):
1.Species: Triplochiton scleroxylon, thermally modified by a proprietary closed-system process using heat and steam only. No chemicals, preservatives or resins.
2.Grade: A & Better Clear.
3.Density: 320 kg/m3 (20 lb/ft3), nominal.
4.Dimensional Stability: Swelling less than 1 percent after 30 days water submersion per ASTM D1037; tangential and radial shrinkage less than 1 percent (EMC to fiber saturation).
5.Decay Resistance: Durability Class 1 (very durable) per CEN/TS 15083-1 and EN 350, and "Highly Resistant" per ASTM D1413 / AWPA E10; average mass loss 0 to 5 percent.
SPECIFIER NOTEThermally modified ayous produced to ThermoWood Thermo-D is rated Durability Class 2 (5 to 10 percent mass loss). Retaining the Class 1 requirement distinguishes the basis-of-design product; comparable products must submit test reports demonstrating Class 1.
6.Hardness: Janka 285 lbf.
7.Fire: Untreated: not rated ASTM E84 Class A or B; not tunnel-tested. CSFM BML Listing 8140-2377:0003 (SFM 12-7A-1, Western Fire Center report 25068r2) for horizontal T&G siding, nominal 1x6 and wider, over sheathing (see specifier note in Part 1).
8.Color: Uniform caramel to amber; weathers to silver-gray if left unfinished.
B.Thermally Modified Nordic Spruce (Basis of Design: Nova Inari):
1.Species: Picea abies, thermally modified to ThermoWood Association product class Thermo-D (212 deg C plus or minus 3 deg C), using heat and steam only.
2.Grade: Select Knotty, equivalent to WCLIB No. 17, paragraph 111-e, f.
3.Density: 440 kg/m3 (27 lb/ft3), nominal.
4.Dimensional Stability: Shrinkage less than 2.0 percent.
5.Durability: Durability Class 2 (durable) per EN 350, suitable for Use Class 3 (outdoors, exposed to weather) per EN 335.
6.Mechanical Properties: MOR 9,500 psi; MOE 1,500,000 psi; Janka 380 lbf.
7.Fire: Untreated: not rated ASTM E84 Class A or B; not tunnel-tested.
C.Thermally Modified Hardwood (Basis of Design: Nova Korina):
1.Species: Terminalia superba (also sold as Frake or Limba), thermally modified by a proprietary closed-system process using heat and steam only. No chemicals, preservatives or resins.
2.Grade: Standard and Better.
3.Density: 600 kg/m3 (37 lb/ft3), nominal.
4.Mechanical Properties (ASTM D143, 12 percent MC): MOR 12,510 psi; MOE 1,520,000 psi; Janka 670 lbf.
5.Dimensional Stability: Swelling and shrinkage less than 2 percent.
6.Decay Resistance: Durability Class 2 (durable) per EN 350, as reported by the producer.
7.Fire: Untreated: not tunnel-tested.
D.Tannin-Free Merbau (Basis of Design: Melywood(R)):
1.Species: Merbau, Intsia bijuga, from Indonesia, modified by the producer's proprietary injection process that neutralizes the tannins in the wood fiber to prevent tannin bleed and staining.
2.Grade: FAS (equivalent to Standard and Better), mixed grain.
3.Density: 750 kg/m3; MOR 16,800 psi; MOE 2,230,000 psi; Janka 1,500 lbf (USDA FPL Wood Handbook).
4.Decay Resistance: Durability Class 1 to 2 against fungi per EN 350; termites Class D (durable).
5.Size: 1 x 6 nominal only, 3/4 x 5-1/2 inches (19 x 140 mm), S4S E4E or milled to [1 x 6 Rainscreen Siding (System A)] [1 x 6 T&G pattern (System B)] as selected.
6.Fire: Untreated: not tunnel-tested.
E.Tropical Hardwoods:
SPECIFIER NOTEValues below are from ASTM D143 small clear specimens at 12 percent moisture content.
Species (Basis of Design)Botanical nameDensityJanka (min.)E84 Class
Batu / Red Balau (Nova Batu)Shorea guiso (red balau group)850 kg/m32,000 lbfA (FSI 25, SDI 65)
Bangkirai / Yellow Balau (Nova Bangkirai)Shorea laevis930 kg/m32,000 lbfA (FSI 25, SDI 110)
Torem (Nova Torem)Manilkara spp.980 kg/m33,000 lbfNot tested
Ipe (Nova Ipe)Handroanthus spp.1,020 kg/m33,000 lbfNot tested
Fijian Mahogany (Nova Genuine Mahogany)Swietenia macrophylla, plantation grown in Fiji650 kg/m3800 lbfNot tested
1.Grade: [FAS Clear (Ipe)] [Standard and Better, equivalent to First Clears / Select and Better, sap-free (Batu, Bangkirai, Torem)] [clear heartwood, essentially sap-free (Fijian Mahogany)], clear one face and two edges.
2.Size (Fijian Mahogany): 1 x 6 nominal only, milled from 19 mm or 21 mm pattern blanks.
2.3SIDING BOARDS - SYSTEM A (RAINSCREEN)
A.Profile: Nova Rainscreen Siding profile per Nova Standard Profiles (www.novausawood.com/standard-profiles; downloadable SVG drawings); grooved both edges to receive concealed clips; eased face edges; square ends.
Nominal sizeOverall widthCoverage width
1 x 43-1/4 in. (83 mm)2.845 in. (72 mm)
1 x 65-1/4 in. (133 mm)4.845 in. (123 mm)
1 x 87 in. (178 mm)6.595 in. (168 mm)
B.Thickness: 0.72 inch (18 mm) net (1x nominal rainscreen profile).
C.Moisture Content at Shipment: Thermally modified species 6 to 8 percent; tropical hardwood pattern stock kiln dried to 10 to 12 percent. Acclimate to project-site equilibrium moisture content before installation, particularly in dry climates.
D.Dimensional Tolerance: Net dimensions plus 0 inch, minus 1/16 inch (1.5 mm) at time of manufacture; boards within a production batch plus or minus 1/64 inch (0.4 mm). Dimensions change with moisture content during acclimation.
E.Lengths: [8 to 20 feet (2.4 to 6.1 m), odd and even lengths] [Specified lengths, cut to length by manufacturer: ].
F.Selected size: [1 x 4] [1 x 6] [1 x 8].
2.4ATTACHMENT SYSTEM - SYSTEM A (RAINSCREEN)
A.Concealed Clips: Nova ExoClad QuickClip; glass-fiber-reinforced nylon 6/6; provides 3/4-inch (19 mm) stand-off without furring strips; allows seasonal movement of boards.
1.Clip Spacing: At every stud or blocking, not more than 16 inches (406 mm) o.c. along each board.
B.Fasteners (not supplied by clip manufacturer): #9 or #10 exterior-grade screws, 2-1/2 inches (64 mm) minimum length, [Type 304] [Type 316] stainless steel, driven through each clip into studs or blocking. Sheathing alone does not provide adequate holding. Type 316 within 20 miles (32 km) of salt water.
SPECIFIER NOTESalt exposure depends on prevailing wind and humidity; 5 to 20 miles is typical. 20 miles is shown as the conservative default; adjust for the site.
C.Vent Strips: Corrugated vent strip with insect screen under the top and bottom rows of siding, Cor-A-Vent SV-3 or equal.
2.5SIDING BOARDS - SYSTEM B (T&G PATTERN SIDING)
A.Profile: Tongue-and-groove pattern siding per Nova Standard Profiles (www.novausawood.com/standard-profiles): [1 x 6] [1 x 8] [Nickel Gap] [Edge V] [Nickel Gap / Edge V Combination] T&G, 3/4 inch (19 mm) net thickness.
B.Wildland-Urban Interface (Ambara): Nominal 1 x 6 or wider in one of the patterns covered by CSFM BML Listing 8140-2377:0003: Nickel Gap / Reverse T&G; WWPA Standard Patterns WP-2, WP-4, WP-8, WP-10, WP-12, WP-14, WP-16, WP-18, WP-20 and 116; Redwood Lumber Patterns No. 17 patterns 16, 17, 18, 616, 617, 633, 633EE, 634, 634EE, 708, 708R, 711, 711R, 712, 712R, 713, 713R, 715, 715R, 716, 716R, 733R and 734R. Nominal 1 x 4, shiplap and square-edge profiles are not covered.
C.Orientation: Horizontal. Vertical application is not covered by the WUI listing.
D.Moisture Content, Tolerance and Lengths: Moisture content at shipment, thermally modified species 6 to 8 percent; tropical hardwood pattern stock kiln dried to 10 to 12 percent. Net dimensions plus 0 inch, minus 1/16 inch (1.5 mm) at time of manufacture. Lengths [8 to 20 feet (2.4 to 6.1 m), odd and even lengths] [specified lengths, cut to length by manufacturer: ]. Acclimate to project-site equilibrium moisture content before installation.
E.Sheathing (by Section 06 16 00): Exterior OSB or plywood, 7/16 inch (11 mm) minimum, over nominal 2 x 4 studs at 16 inches o.c. maximum, as required by the WUI listing.
F.Fasteners: 6d ring-shank siding nails, [Type 304] [Type 316] stainless steel, one nail per stud just below each horizontal joint, penetrating sheathing and framing. Use Type 316 within 20 miles (32 km) of salt water.
2.6ACCESSORIES
A.Trim: Outside corners, inside corners, and window and door casings of the same species as siding, [mitered] [overlapping corner boards] [rabbeted], as detailed.
B.End-Grain Sealer: Nova ExoWax end sealer, applied to all field-cut ends and any field-drilled holes.
2.7FINISH
SPECIFIER NOTEManufacturer's warranty for clip-attached (hidden-fastener) siding requires an approved oil-based exterior finish on all sides. Do not select "unfinished" with the clip system.
A.Finish: [Unfinished, allowed to weather (face-fastened installations only)] [Nova ExoShield penetrating tung oil finish on all four sides, color: [Clear] [Natural] [Mahogany] [Walnut] [Black Walnut] [Platinum] [Antique Bronze] [Custom], [factory applied] [field applied per Section 09 93 00]] [Other finish selected by Architect: , factory applied by manufacturer].
SPECIFIER NOTENova factory-applies ExoShield and, on request, other penetrating finishes (for example Cutek, Renner, Sansin, Penofin, Messmer's, Seal-Once, Ready Seal). Nova states performance only for ExoShield: recoat siding at 3 to 5 years and decking at 1 year. Maintenance intervals for other finishes vary by product, from 6 months to 1 year on decking.

PART 3 - EXECUTION

3.1EXAMINATION
A.Verify that sheathing, weather barrier, flashings, and window and door installations are complete and that framing is plumb and true within 1/4 inch in 10 feet (6 mm in 3 m).
B.Verify clearance required by manufacturer's warranty from bottom of siding to grade, paving or other hard surface: not less than 6 inches (152 mm) for thermally modified species and 16 inches (406 mm) for tropical hardwoods.
C.Proceed with installation only after unsatisfactory conditions have been corrected.
SPECIFIER NOTEInadequate acclimation is the most common cause of field problems with solid wood: open joints, cupping and buckling. Retain the acclimation hold point below.
D.Acclimation: Do not begin installation until the Architect has received an Acclimation Record showing average moisture content within 2 percent of the site equilibrium moisture content. Material installed without an Acclimation Record will be rejected.
3.2INSTALLATION
A.System A: Install in accordance with Nova's "ExoClad QuickClip Installation Guide" (https://www.novausawood.com/PDFs/ExoClad-QuickClip-Installation-Guide.pdf) [and "Ambara Siding Installation Guide" (https://www.novausawood.com/PDFs/Ambara-Installation-Guide.pdf)] [and "Inari Siding Installation Guide" (www.novausawood.com/downloads)], current edition at time of bid (guides are revised quarterly).
B.System A: Install vent strips at bottom and top of cavity before siding.
C.Install corner and opening trim before siding.
D.Attach clips with specified fasteners at spacing indicated on approved Shop Drawings. Do not face-nail or face-screw boards except at locations permitted by manufacturer.
E.Install boards level and true with consistent reveal. Stagger butt joints; locate joints over clips.
F.Seal all field-cut ends with ExoWax immediately after cutting.
G.System B: Install horizontally over weather barrier and sheathing in accordance with Nova's "Ambara Siding Installation Guide" (https://www.novausawood.com/PDFs/Ambara-Installation-Guide.pdf). Face-nail with one nail per stud just below each horizontal joint; make butt joints tight and over studs; stagger joints. In WUI areas, install exactly as listed under CSFM BML Listing 8140-2377:0003; do not substitute profiles, sheathing or orientation.
3.3CLEANING AND PROTECTION
A.Remove debris and marks with cleaners recommended by the manufacturer. Protect installed siding from damage until Substantial Completion; replace boards that cannot be repaired.

END OF SECTION